Module 8 · Lesson 3

4–20 mA loops, calibration and loop checks

Wire, calibrate and commission current loops from field instrument to control-system display.

Learning outcomes

  • Explain the key principles of 4–20 ma loops, calibration and loop checks.
  • Carry out a structured practical check or configuration task.
  • Recognise common faults, risks and evidence needed for diagnosis.

Before you begin

Loop calibrator, drawings and calibration sheet.

Safety: Use site procedures, approved test equipment and competent supervision. Never bypass a protection or interlock without formal control.

Step-by-step learning

  1. Verify loop supply and calculate available voltage for all loads.
  2. Isolate or place the loop in a safe maintenance state.
  3. Apply 0, 25, 50, 75 and 100 percent values and record as-found/as-left results.
  4. Complete an end-to-end loop check including alarms, trips and display.
Ian's practical tips:
  • A loop check proves the whole chain; bench calibration proves only the instrument.
  • Always restore impulse lines, manifolds and software overrides after calibration.

Fault-finding questions

  • What should be happening, and what evidence proves it?
  • Where is the last known correct signal, voltage, state or process condition?
  • What changed immediately before the fault?
  • Can the system be divided into smaller testable sections?

Practical activity

Create a one-page test record for this lesson. Include expected values, measured results, equipment used, risks controlled, defects found and the final proven condition.