Module 8 · Lesson 4

Instrument fault finding and signal quality

Diagnose noisy, drifting, frozen, saturated, intermittent and implausible process signals.

Learning outcomes

  • Explain the key principles of instrument fault finding and signal quality.
  • Carry out a structured practical check or configuration task.
  • Recognise common faults, risks and evidence needed for diagnosis.

Before you begin

Trend data, calibrator, meter and loop documentation.

Safety: Use site procedures, approved test equipment and competent supervision. Never bypass a protection or interlock without formal control.

Step-by-step learning

  1. Compare process reality, local indication, loop current, PLC raw value and SCADA value.
  2. Check power, polarity, shielding, grounding and moisture ingress.
  3. Inspect process connections for blockage, bubbles, condensation or plugging.
  4. Substitute a known signal to separate field and control-system faults.
Ian's practical tips:
  • Work from the process toward the display in measured steps.
  • Never “calibrate out” a process-connection problem.

Fault-finding questions

  • What should be happening, and what evidence proves it?
  • Where is the last known correct signal, voltage, state or process condition?
  • What changed immediately before the fault?
  • Can the system be divided into smaller testable sections?

Practical activity

Create a one-page test record for this lesson. Include expected values, measured results, equipment used, risks controlled, defects found and the final proven condition.

← Previous LessonLesson 32 of 60 · Module 8: Instrumentation & Process MeasurementNext Lesson →